Page:
|
1 of 2 FX292
|
Spec. No.
|
P5.2.1
|
Dated:
|
September 5, 2001
|
Issue:
|
1
|
Sarnia:
Technical:
|
1-800-265-7514
1-800-585-8857
|
|
1. |
GENERAL |
|
1.1 |
This standard sets forth specifications
and acceptable products for rigid, semi-rigid and flexible
insulation for use on odd shaped, cylindrical and flat equipment. |
|
1.2 |
This standard covers systems operating
at temperatures ranging from ambient to 1200 ºF (649 ºC). |
| |
1.3 |
This standard will address wall thickness
and multiple layer recommendations. |
2. |
APPLICATIONS |
| |
2.1 |
HIGH TEMPERATURE EQUIPMENT 600°F (316°C) to 1200°F
(649°C)
A thermal calculation should be performed
to determine the proper insulation thickness to ensure
either personnel protection or process control. Where
the insulation thickness exceeds 3", a multiple layer
system is recommended.
|
| |
2.1.1 |
COMPOSITION:
Basalt wool and organic binder which is non-combustible and
asbestos free. |
| |
2.1.2 |
NOMINAL DENSITY:
The nominal density to be between 6 and 12 pcf. |
| |
2.1.3 |
MAXIMUM THERMAL CONDUCTIVITY:
The thermal conductivity shall not exceed the following
for any density:
BTU in./hFt2°F (W/m K)
|
Mean temperature
|
0.44 (0.064)
|
400°F (204°C)
|
0.53 (0.076)
|
500°F (260°C)
|
0.66 (0.095)
|
600°F (316°C)
|
|
| |
2.1.4 |
MAXIMUM NON-FIBROUS (SHOT) CONTENT:
The percentage content of non-fibrous material (shot) shall
not exceed 20% by weight (ASTM C 1335) |
| |
2.1.5 |
LINEAR SHRINKAGE:
The linear shrinkage, when tested at 1200°F (649°C), shall be
less than 1%. |
|
2.1.6 |
STRESS CORROSION:
The material must not promote or contribute to the corrosion
of austenitic stainless steel. |
| |
2.1.7 |
SURFACE BURNING CHARACTERISTICS:
Shall not exceed
Flame Spread 5 Smoke Developed 0 |
| |
2.1.8 |
NOISE REDUCTION COEFFICIENT:
The NRC shall not be less than 0.95 |
APPROVED MANUFACTURE (S): FIBREX INSULATIONS,
INC. or equal
Single or multiple layer -
FBX INDUSTRIAL BOARD
FBX INDUSTRIAL FLEXIBLE BATT |
| |
2.2 |
LOW TEMPERATURE EQUIPMENT AMBIENT TO 599°F
(315°C)
A thermal calculation should be performed to determine the
proper insulation thickness to ensure either personnel protection
or process control. |
| |
2.2.1 |
COMPOSITION:
Basalt wool and organic binder which is non-combustible and
asbestos free. |
| |
2.2.2 |
NOMINAL DENSITY:
The nominal density to between 3 and 12 pcf. |