Page:
|
1 of 2 FX293
|
Spec. No.
|
P5.2.3
|
Dated:
|
September 5, 2001
|
Issue:
|
1
|
Sarnia:
Technical:
|
1-800-265-7514
1-800-585-8857
|
|
1. |
GENERAL |
|
1.1 |
This standard sets forth specifications
and acceptable products for rigid, semi-rigid, and flexible
insulation for use on tanks. |
|
1.2 |
This standard covers systems operating
at temperatures ranging from ambient to 1200 ºF (649 ºC). |
| |
1.3 |
This standard will address wall thickness
and multiple layer recommendations. |
2. |
APPLICATIONS |
| |
2.1 |
VESSEL WALL INSULATION
A thermal calculation should be performed
to determine the proper insulation thickness to ensure
either personnel protection or process control. Where
the insulation thickness exceeds 3", a multiple layer
system is recommended.
|
| |
2.1.1 |
COMPOSITION:
Basalt wool and organic binder which is non-combustible and
asbestos free. |
| |
2.1.2 |
NOMINAL DENSITY:
The nominal density to be between 6 and 12 pcf. |
| |
2.1.3 |
MAXIMUM THERMAL CONDUCTIVITY:
The thermal conductivity shall not exceed the following
for any density:
BTU in./hft2°F (W/m K)
|
Mean temperature
|
| 0.33 (0.048) |
200°F (93°C) |
0.43 (0.062)
|
300°F (149°C)
|
0.54 (0.078)
|
400°F (204°C)
|
0.67 (0.097)
|
500°F (260°C)
|
|
| |
2.1.4 |
MAXIMUM NON-FIBROUS (SHOT) CONTENT:
The percentage content of non-fibrous material (shot) shall
not exceed 20% by weight (ASTM C 1335) |
| |
2.1.5 |
LINEAR SHRINKAGE:
The linear shrinkage, when tested at 1200°F (649°C), shall be
less than 1%. |
|
2.1.6 |
STRESS CORROSION:
The material must not promote or contribute to the corrosion
of austenitic stainless steel. |
| |
2.1.7 |
SURFACE BURNING CHARACTERISTICS:
Shall not exceed
Flame Spread 5 Smoke Developed 0 |
| |
2.1.8 |
NOISE REDUCTION COEFFICIENT:
The NRC shall not be less than 0.95 |
| |
2.1.9 |
WATER VAPOR SORPTION:
The water vapor sorption shall be less than 1% by weight. |
APPROVED MANUFACTURE (S): FIBREX INSULATIONS,
INC. or equal
Single or multiple layer -
FBX INDUSTRIAL BOARD
FBX INDUSTRIAL FLEXIBLE BATT |
| |
2.2 |
TANK TOP INSULATION
A thermal calculation should be performed to determine the
proper insulation thickness to ensure either personnel protection
or process control. Where the insulation thickness exceeds
3", a multiple layer system is recommended. |
| |
2.2.1 |
COMPOSITION:
Basalt wool and organic binder which is non-combustible and
asbestos free. |
| |
2.2.2 |
NOMINAL DENSITY
The nominal density to be between 8 and 12 pcf. |